More shine positive pressure air breathing apparatus
Model:SAC1100-SERIES,RHZKF6.8/30,RHZKF9/30,G-F-20
WARNING: Only close
observance of the instruction laid out in this booklet can guarantee safe use
of the apparatus and perfect service. Breathing apparatus must be employed by
specially trained people under supervision of person well aware of its limits
of application and of the laws in being.
1、 Application
field
VOLER position pressure air breathing
apparatus is designed for the use in fire fight application, chemical industry,
metallurgy, mines, petrol industry, rescue operation, maintenance works and
polluted area wherever there is or may be oxygen deficiency, It protects users from toxic gas, particles and
mist, word in environment with less oxygen content than 17%,or fog caused by
fire accident.
2、 product
description
VOLER positive pressure air breathing
apparatus is composed of the following parts:
Air is compressed in the cylinder(pressure
of 30MPa).Compressed air is reduced to (0.75±0.15) MPa through
the pressure reducer, and led to medium pressure hose. Then it is reduced in
pressure again through the demand valve and provided to user through full mask.
The outside toxic gas or particles can not
get inside because the pressure inside the mask is always higher than the
atmospheric pressure. Thus the tightness of the face mask is guaranteed.
2.1 Full mask
Full mask is specially designed for Asian
face, ensuring comfort and good seal that provides an efficient tightness
2.2 Demand valve
The demand valve provides air to the wearer
depending on the air breathing need of the wearer. It ensures a higher air
pressure inside the face mask than outside pressure.
The demand valve can be manually switched
off thanks to the switcher(C) on the top of the valve, and then no air is
provide to the face mask. The demand valve is automatically switched on at the
first inhalation of the wearer.
At the central bottom of valve, there is a
manual control air supply button(D) to be used to:
-Switch on the demand valve manually;
-Gave an additional breath of air if the
wearer feels supply deficiency.
Besides, it can release the remaining air
inside the medium pressure hose which is more convenient for test and
disassembly of the quick connector.
2.3 Pressure reducer
The pressure reducer is made of brass with
anticorrosive coating. Compressed air is reduced in pressure by the pressure
reducer to (0.75±0.15)MPa. Pressure reducer delivers a constant and stable pressure during
the life time of the cylinder. Pressure reducer is connected to :
-Cylinder;
-Medium pressure hose which is connected to
demand valve and providing air;
-High pressure hose which is connected to
pressure gauge.
2.4 Safety valve
Safety valve locates on the pressure
reducer. When medium pressure is overhigh, the safety valve switches on
automatically to release air, and switches off after medium pressure reduces
too normal value.
It is regulated in the norm GA124-2004 “fire
fighting positive pressure air breathing apparatus ” that, opening pressure and
fully exhausting pressure of safety valve should be within 110% to 170% of
maximum designing output pressure of pressure reducer; and the closing pressure
of safety valve is no less than maximum designing output pressure. That is :
Safety valve opening pressure and fully exhausting
pressureL0.99-1.53)MPa
Safety valve closing pressure:≥0.09MPa.
2.5Pressure gauge and warning device
The scale of pressure gauge is (0-40)MPa. The
gauge connects to pressure reducer through high pressure hose. Fluorescent
material is used in dial plate, which enables the pressure value to be read
clearly in dark. The watchcase takes high anti-impact material, with rubber
protective cover, to be water proof, shock
proof and anti dust. The warning device locates on the high pressure hose near
pressure gauge, which actuates the audible warning when cylinder pressure drops
to (5.5±0.5)MPa. From the beginning of the warning, the user has to leave
the polluted area immediately, and then plug a new cylinder if needed.
2.6Back plate assembly with harness
Back plate assembly includes back plate,
harness, waist belt, buckle, pressure reducer holder and cylinder tightening
belt. Injected with flame resistant plastic and carbon fiber material, the back
plate is compact, light, high mechanical resistant, and anti-impact. It is
designed to fit human body’s back, notably regarding ergonomics and comfort. All
the components of the back plate assembly are fire retardant treated.
2.7 Medium pressure hose
The medium pressure hose is linked to the
pressure reducer and to the demand valve. It is made from flame resistant
rubber. The explosion pressure is 4MPa,more than 4 times of maximum output
pressure from pressure reducer.
The cylinder is made from fully wrapped
carbon fibre reinforce aluminum lined. With 6.8L’s capacity, it ensures 1 hour
of moderate activity in real use.
3.0 Operation sequence
3.1 Cylinder connecting
The assembly can accept one cylinder with
maximum capacity for 12L, or two 6.8L cylinders. Fpr two cylinders, there needs
to be double cylinder holder and two inhalation mouths, and the length of the
tightening belt should be increased.
A)
Cylinder valve is well closed;
B)
Put the cylinder into the
groove of central back plate, and connect firmly the cylinder to pressure
reducer;
C)
Fasten the belt buckle of
cylinder.
3.2 Demand valve connecting
Snap the medium pressure demand valve and
reducer hoses together.
Connector is securely locked. To disconnect
apply a slight axial force while sliding back the female connector ring. Don’t
disconnect when the hose is under pressure. Press button on the demand valve to
avoid air leaks when donning the set.
3.3 Quick check before use
(before use, the following sequences should be followed to avoid danger)
A) Pressure of compressed air in the
cylinder:
With valve fully opened, the valve of
pressure gauge is 30 MPa, under 30MPa and 20℃.Otherwise , the
effective using time will be shortened.
B)Air-tightness of cylinder:
It is regulated in the norm GA124*2004 that
when open and close the pressure gauge, pressure drop on the gauge should be no
more than 2MPa within one minute.
D)
Warning system:
-Close the demand valve;
-Open cylinder valve to fill the hose with
air, and then close it ;
-Open demand valve manual control button, vent
the air off slowly with hand palm and observe the value change of pressure
gauge;
-The warning system start working when the
pressure gauge shows(5.5±0.5)MPa.
3.4 Donning the set
A) Adjusting the back plate
Set the shoulder straps at maximum length:
don the set and pill down the straps tips until the back plate rests
comfortably on the user’s back.
Fasten waist belt, and pull the free end of belt till the desired
tension and comfort.
B)Donning the mask
Hold the mask by one hand till fully with the face, and pull
the headband by the other hand to cover the head; pull the band till full fit
and comfort.
Plug the demand valve into the mask and inspire.
If it is impossible to breathe and mask fully fits the face, then the mask is
well air-tight. It is necessary to avoid the facial hair between mask and face
for fully fit.
3.5 During use
When in use check from time the pressure
gauge and plan the work load to suit the air left in the cylinder. With a 6.8L
cylinder the breathing apparatus can last for 10 minutes after the warning has
started. Then the user must leave the polluted area immediately.
In case of emergency, extreme condition or
the user needs extra air supply, the manual control button can be opened to
release bigger flow of air supply.
3.6 After use
A) Close the cylinder valve;
B)Disconnect demand valve from the mask, and
the excess air will be vented off;
C)Unfasten waist belt ad slide back the
shoulder straps;
D)Place the set and cylinder up, on a clean
surface.
4.Maintenance
4.1Cylinder
The cylinder must receive regular check
according to related national laws and regulations, and be tested by
professional authorized institute and personnel; records should be checked foe
leaks and pressure reducer connector for tightness.
A)
Cylinder filling air has to
follow EN132 norm, specification as below:
Requirement on humidity: moisture inside cylinder should be
o more than 35g/m3 under 30MPa working pressure.
B)
Cylinder valve has to be kept
shut down after end of use for refilling to prevent moisture from getting in .
Don’t empty air in cylinder and a pressure of at least 0.5MPa should remain. If
the cylinder is empty with air, it has to be dried before charging: air drier
or cylinder kiln can be used, with maximum drying temperature 90℃.
C)
Cylinder should b place up
(cylinder valve upwards) during transport and storage. When being carried , the
cylinder should be held closely by both hands and it is strictly forbidden to
hold the cylinder by handwheel. Cylinder by handwheel. Cylinder should be
protected from iMPact, rolling, cast and shock.
Element
|
Percentage
of weight(dried air)
|
Percentage
of volume(dried air)
|
Oxygen
|
23.01%
|
20.93%
|
Nitrogen
|
75.51%
|
78.10%
|
Argon
|
1.29%
|
0.9325%
|
Carbon
dioxide
|
0.04%
|
0.03%
|
Hydrogen
|
0.001%
|
0.01%
|
Neon
|
0.0012%
|
0.0018%
|
Helium
|
0.00007%
|
0.0005%
|
Krypton
|
0.0003%
|
0.0001%
|
Xenon
|
0.00004%
|
0.000009%
|
4.2 Cleaning and disinfecting
A)Harness on back plate can be removed for
cleaning and disinfecting;
B)During washing, lukewarm water and
neutral detergent should be used; The concentration and duration of use should
follow the instruction of the detergent.
Corruption from detergent to components of
breathing apparatus should be avoid: organic solvent will damage rubber or
plastic parts.
D)
After cleaning and
disinfecting, all components should be sired under 15℃ to 30 ℃.Any heat
radiation source should be avoided like sunshine, drying machine, heater ect.
Compressed air is recommended for use for airing ok key components like
pressure reducer and medium pressure hose, to remove the potential humidity.
4.3 Testing
Test to the breathing apparatus is need
after each cleaning and maintenance.
If the film of demand valve or any rubber
parts shows damage or aging(being sticky, hardened or crinkled), it should be
changed immediately.
Low pressure air-tightness test and demand
valve static positive pressure test must be done in accordance with norm
4.4 Storage
Only after cleaning, disinfecting,
checking, maintaining and recording , breathing apparatus can be stores in
non-dust, shady and cool place under room temperature, and away from sunshine,
heat source, humidity and corrosive substance.
Storage temperature has to be within 15℃ to 30 ℃ and the
environment needs to be dry. Besides, breathing apparatus should be kept in
cases of good tension resistance.
Staffs without special training are
forbidden to step in the storage room. After storage and before each use, make
sure that working environment will not damage products property and test to all
the components has been done. It is strictly forbidden for the users to
disassembly or misuse the equipment.
4.5 Transportation
Breathing apparatus should be kept in the
original package or transportation case, and
no special requirement is needed. Please also follow the storage
instruction.
5.Maintenance, test and record
5.1 Requirement on test: Please see the table below
Part
|
Activity
|
1
|
2
|
3
|
4
|
5
|
6
|
Complete
set
|
Cleaning
|
|
|
/
|
|
|
|
Complete
set
|
Function,
tightness
|
|
/
|
/
|
|
/d
|
|
Complete
set
|
Back
plate check
|
/
|
|
|
|
|
|
Demand
valve
|
Cleaning
|
|
/
|
|
|
|
|
Demand
valve
|
Disinfecting
|
|
|
|
|
/c
|
|
Demand
valve
|
Membrane
check
|
|
|
|
|
/c
|
|
Demand
valve
|
Member
replacement
|
|
|
|
|
|
/a
|
High
pressure connector
|
Testing pressure(pressure gauge)
|
|
|
|
|
/
|
|
High
pressure connector Oring
|
Replacement
|
|
|
|
|
/c
|
|
Pressure
reducer
|
Revision
|
|
|
|
/
|
|
|
Cylinder
|
Testing
|
|
|
|
|
|
/d
|
Full
mask
|
Cleaning
|
|
|
/c
|
|
|
|
Full
mask
|
Testing
|
|
|
|
|
/
|
|
1:Before allowing the use;2:Before
use;3:After use;4:Every six months;5:Annually;6:Every three years
a)
The set been used; b) Other
breathing apparatus; c)After use in corrosive areas or in extreme ambient
conditions; d)In accordance with national regulations.
Warning: every time the valve is
disassembled/assembled from/to the cylinder for maintenance and/or testing ,
the valve shall be changed. Please refer to the specific information notice
that comes with the cylinder or to the label of composite cylinder.
After the replacement of any part
whatsoever it is mandatory to perform all on function and pneumatic tightness.
5.2 Daily maintenance record
Please see the table below:
Name
|
Date
|
hand
band
|
Cylinder
valve
|
Pressure
reducer
|
Demand
valve
|
Mask
|
||||||||||
|
|
Disinfect/cleaning
|
Eyrballing
|
Parts change
|
Disinfect/cleaning
|
Eyrballing
|
Parts change
|
Disinfect/cleaning
|
Eyrballing
|
Parts change
|
Disinfect/cleaning
|
Eyrballing
|
Parts change
|
Disinfect/cleaning
|
Eyrballing
|
Parts change
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6.Common faults and measures
Warning: the positive air
breathing apparatus is essential for user’s life, thus the staff in charge of
maintenance must receive special training from manufacturer and get
qualification accordingly.
Component
|
Faults
|
Possible cause
|
Measures
|
High
pressure parts
|
Air leakage at connection points
|
1.connction untight
|
Fasten again
|
2.demage of sealing parts
|
Replace sealing parts
|
||
Warning device
|
No warning under(5.5±0.5)MPa
|
1.position change of warning wistle
|
Readjst position fo whistle
|
2.whistle blocked or dirty
|
Clean the whistle
|
||
Pressure reducer
|
Air leakage at soft hose connection
|
Damage of O ring
|
Replace o RING
|
Air leakage at safety valve
|
1.damage of high pressure sealing
|
Replace damaged parts
|
|
|
2.air leakage of valve
|
Replace for new one
|
|
Cylinder valve
|
Air leakage at handwheel
|
1.damage of sealing
|
Replace sealing parts
|
Close non-tihghtly or air non-smoothly
|
1.damage of valve core due to too much
pressure
|
Replace valve core
|
|
2.damage of main valve body
|
Replace main body
|
||
Air leakage at cylinder neck
|
Damage of O ring
|
Replace O ring
|
|
Demand valve
|
Air deficiency
|
Inner struction fault
|
1.send back to manufacturer
|
Abnormal air supply or supply while
unconnected to mask
|
|
2.repair by special trained person
|
Delta Plus reserves the right to explain
and modify this instruction.